Installation
2106M0525 Iss 2 Nov 05 12
Mounting
Caution The enclosure must be fixed in position using the external mounting
lugs and not mounted using any type of cable entry device.
Sensepoint should be fitted to a flat firm surface suitable for the unit’s size and weight, e.g. a wall,
as follows:
1 Drill two mounting holes in the surface.
The surface should be flat and firm. For sizes, position, etc. see the previous dimension
drawing.
2 Mount the detector using its two mounting lugs.
Use M6 screws/bolts. Mount the unit with the gas sensor pointing downwards to ensure that
dust/water will not collect on the sensor, and to stop gas entering the detector.
Toxic/Oxygen
205.0 mm (8.1”)
76.5 mm (3.0”)
34.0 mm (1.3”)
Sensor
Cap
Enclosure
Sensor
Flammable
195.0 mm (7.7”)
Note Diagram not to
scale