5895XL Board and Terminal Strip Description Before You Begin Installing
Terminal # and Label Description
Rating
Voltage Current
1 L AC input (hot) 120 VAC,50/60 Hz 2.7 A
2 G Earth ground N/A N/A
3 N AC input (neutral) 120 VAC,50/60 Hz 2.7 A
4 X I/O 6
1
1 Regulated/special application when used for releasing
Flexput Circuit 24 VDC 3.0 A Notification Circuits
5O 100 mA Initiation Circuits
6 X I/O 5* Flexput Circuit 24 VDC 3.0 A Notification Circuits
7 O 100 mA Initiation Circuits
8 X I/O 4* Flexput Circuit 24 VDC 3.0 A Notification Circuits
9O 100 mA
Initiation Circuits
10 X I/O 3* Flexput Circuit 24 VDC 3.0 A Notification Circuits
11 O 100 mA Initiation Circuits
12 X I/O 2* Flexput Circuit 24 VDC 3.0 A Notification Circuits
13 O 100 mA Initiation Circuits
14 X I/O 1* Flexput Circuit 24 VDC 3.0 A Notification Circuits
15 O 100 mA Initiation Circuits
16 B SBUS OUT SBUS communication 5 VDC 100 mA
17 A
18 + SBUS power 24 VDC 1.0 A
19 -
20 B SBUS IN Used for Class A installations
21 A
22 +
23 -
24 N.C. RELAY 2 General Purpose Relay 2 24 VDC 2.5 A
25 C
26 N.O.
27 N.C. RELAY 1 General Purpose Relay 1 24 VDC 2.5 A
28 C
29 N.O.
30 B SBUS IN/
OUT
5895XL communication with main
panel or to controlling 5895XL if
daisy-chained
5 VDC 100 mA
31 A
32 + MAIN 5895XL SBUS power (from FACP) 24 VDC 10 mA
33 -
Table 2.1 Terminal Strip Description and Electrical Ratings