6 5895XL Manual — P/N 151142-L8:M 2/15/2022
Section 1: Overview
1.1 5895XL Description
The Model 5895XL Intelligent Power Module provides additional power and circuits to the 6820, 6820EVS, 6808, 6700, 5820XL, 5820XL-
EVS, 5808, and 5700 FACPs. The 5895XL can power all compatible modules, including SLC devices (via a 5815XL or 6815 SLC
Expander), remote annunciators (6860, 6855, and 5860), notification appliances, auxiliary power modules, and all other compatible mod-
ules.
The 5895XL has six Flexput circuits and two programmable relays. Outputs are rated 3.0 A (6.0 A total for each 5895XL). Relays are Form
C rated at 2.5 A @ 24 VDC. Outputs and relays are fully programmable.
The 5895XL is optically isolated, providing ground loop isolation and transient protection. It functions as an SBUS repeater which condi-
tions the RS-485 signal and allows the module to drive up to 6,000 feet of additional SBUS wiring.
The 5895XL is housed in a metal cabinet that is identical in size to the IntelliKnight 5820XL FACP cabinet. This cabinet is large enough to
house two 17 AH batteries. The 5895XL cabinet provides mounting studs for two Model 5815XL or 6815 SLC Expander modules.
The 5895XL communicates to the main FACP via the SBUS. Each 5895XL provides an additional 6,000 feet of SBUS wiring length to the
main panel. As the drawings on the next pages illustrate, this allows for the distribution of modules, SLC devices, and outputs throughout an
extremely large facility.
As well as expanding the wiring length capabilities of the FACP, the 5895XL also expands the power capabilities by an additional 6.0 A of
current.
1.1.1 Maximum Number of SBUS Modules
The chart below shows the maximum number of compatible modules that can be used in an Intelligent installation. Modules can be distrib-
uted among the main panel SBUS and each additional 5895XL SBUS in virtually any combination.
NOTE: The 5700, 6700, 5808 and 6808 do not use 5815XL or 6815 SLC expanders.
Module or Device Maximum Number
5895XL Intelligent Power Module
8 per 5700, 5808, 6700, and 6808installation
16 per 6820/6820EVS installation
5860 or 6855 Remote Annunciator
8 per 6700 installation
12 per 6808 or 5820XL/EVS installation
16 per 6820/EVS installation
6860 Remote Annunciator 16 per 6820/EVS installation
6815 SLC Expander 63 per 6820/EVS installation
5815XL SLC Expander
3 per 5820XL/EVS installation
63 per 6820/EVS installation
5824 Serial/Parallel Modules
4 per 6700, 6808, 6820/EVSinstallation
2 per 5700, 5808, 5820XL/EVS installation
Outputs 6 per 5820XL, 6820/EVS, or 5895XL
Conventional Relays 2 per 5820XL, 6820/EVS, or 5895XL