5895XL Manual — P/N 151142-L8:M 2/15/2022 27
Connecting SBUS Modules to the 5895XL Installation
3.7 Connecting SBUS Modules to the 5895XL
1. Connect SBUS modules to the 5895XL as shown in Figure 3.8 or Figure 3.9.
2. All SBUS modules must have an ID. Use the DIP switches on the module board to assign an ID number (1-31) to the module. This
number identifies the module to the 5895XL and must be unique.
3. Software configuration steps vary for each SBUS module. For more information, refer to the FACP installation manual.
.
3.8 Flexput I/O Circuits
The six Flexput circuits are an innovative and versatile feature of the 5895XL panel. They can be used as: Class A or Class B notification cir-
cuits, Class A or B initiation circuits (either 2-wire or 4-wire detectors), or as auxiliary power circuits (resettable, continuous, or door
holder).
This section of the manual explains how to install the conventional notification appliances and the initiating devices to be used with the
5895XL.
33
-
MAIN SBUS IN/OUT
32 31 30
+AB
29 2628 2527 24
N.O. N.O.CCN.C. N.C.
RELAY 1 RELAY 2
23 1922 1821 1720 16
--++AABB
SBUS IN SBUS OUT
151413121110987654
O
O
X
X
OXOXOXOX
I/O 1 I/O 2 I/O 3 I/O 4 I/O 5 I/O 6
-
+
A
B
Figure 3.8 SBUS Class A Connection to 5895XL
5895XL
SBUS module
33
-
MAIN SBUS IN/OUT
32 31 30
+AB
29 2628 2527 24
N.O. N.O.CCN.C. N.C.
RELAY 1 RELAY 2
23 1922 1821 1720 16
--++AABB
SBUS IN SBUS OUT
151413121110987654
O
O
X
X
OXOXOXOX
I/O 1 I/O 2 I/O 3 I/O 4 I/O 5 I/O 6
-
+
A
B
Max. wire length 6,000 feet.
(Refer to wiring specification
section for details.)
5895XL
SBUS module
Figure 3.9 SBUS Class B Wiring to 5895XL