5895XL Manual — P/N 151142-L8:M 2/15/2022 13
Calculating Current Draw and Standby Battery Before You Begin Installing
Maximum Battery Standby Load
Table 2.3 shows the maximum battery standby load for the 5895XL based on 24 and 60 hours of standby. The numbers below have a built in
20% derating factor for the battery amp-hour capacity. The standby load calculations of line G in the Current Draw Calculation Worksheet
must be less than the number shown in Table 2.3 for the battery size used and standby hours required.
2.5.2 Current Draw Worksheet for SK SLC Devices
For each 5895XL in the installation, use this worksheet in Table 2.4 to determine current requirements during alarm/battery standby opera-
tion. See individual FACP manual for maximum number of devices.
Rechargeable
Battery Size
Max. Load for 24 hrs. Standby,
5 mins. Alarm
1
Max. Load for 60 hrs. Standby,
5 mins. Alarm
1 Required for NFPA 72 Auxiliary Protected Fire Alarm systems for Fire Alarm Service (City Box) and Remote
Station Protected Fire Alarm systems (Polarity Reversal) and Digital Alarm Communicator/Transmitter (DACT)
7 AH 270 mA 105 mA
12 AH 475 mA 190 mA
17 AH 685 mA 270 mA
33 AH 1370 mA 540 mA
Table 2.3 Maximum Battery Standby Load
NOTE: The maximum battery size for FM (Factory Mutual) installations is 33AH.
Device # of Devices Current per Device
Standby
Current
Alarm Current
For each device use this formula: This column X This column = Current per number of devices.
5895XL Intelligent Power Module
(Current draw from battery)
1 Standby 40 mA 40 mA
Alarm: 160
mA 160 mA
Additional 5895XL
(Daisy-chained to this module)
(7 max.) Standby 10 mA mA
Alarm: 10 mA mA
Addressable SLC Detectors
SK-PHOTO
Standby: 0.3 mA
Alarm: 6.5 mA
1
mA mA
SK-PHOTO-T mA mA
SK-PHOTO-R mA mA
SK-HEAT mA mA
SK-HEAT-HT mA mA
SK-HEAT-ROR mA mA
SK-ACCLIMATE mA mA
SK-PHOTO-W
Standby: 0.2 mA
Alarm: 4.5 mA
1
mA mA
SK-PHOTO-T-W mA mA
SK-PHOTO-R-W mA mA
SK-HEAT-W mA mA
SK-HEAT-HT-W mA mA
SK-HEAT-ROR-W mA mA
SK-BEAM (without integral test) SLC Standby/Alarm: 2 mA mA mA
Aux. Pwr Standby: 2 mA mA
Alarm: 8.5 mA mA
SK-BEAM-T
2
(with integral test) SLC Standby/Alarm: 2 mA mA mA
Aux. Pwr Standby: 2 mA mA
Alarm: 8.5 mA mA
OSI-RI-SK SLC Standby/Alarm: 20 mA mA mA
Aux. Pwr Standby: 22 mA mA
Alarm: 20 mA mA
SK-FIRE-CO SLC Standby: 0.30 mA mA
Alarm: 7 mA mA
Table 2.4 Current Draw Worksheet for SK SLC Devices