14 5895XL Manual — P/N 151142-L8:M 2/15/2022
Before You Begin Installing Calculating Current Draw and Standby Battery
SK-FIRE-CO-W SLC Standby: 0.20 mA mA
Alarm: 4.5 mA mA
SK-PTIR-W SLC Standby: 0.20 mA mA
Alarm: 4.5 mA mA
Addressable SLC Modules
SK-MONITOR Standby/Alarm 0.375 mA mA mA
SK-MINIMON Standby/Alarm 0.375 mA mA mA
SK-PULL-SA/SK-PULL-DA Standby/Alarm 0.3 mA mA mA
SK-MONITOR-2 Standby/Alarm: 0.75 mA mA mA
SK-MONITOR-10 Standby/Alarm: 3.5 mA mA mA
SK-CONTROL SLC Standby 0.375 mA mA
Alarm: 0.375 mA mA
Aux Pwr Standby 1.7 mA mA
Alarm: 6.5mA mA
SK-CONTROL-6 SLC Standby 2.65 mA mA
Alarm: 35 mA mA
Aux Pwr Standby 8 mA mA
Alarm: 20 mA mA
SK-RELAY Standby/Alarm: 0.255 mA mA mA
SK-RELAY-6 Standby: 1.9 mA mA
Alarm: 32 mA mA
SK-RELAYMON-2 Standby: 1.3 mA mA
Alarm: 24 mA mA
SK-ZONE Aux Pwr Standby 12 mA mA
Alarm: 90 mA mA
SLC Standby: 0.27 mA mA
Alarm: 5.1 mA
SK-ZONE-6 Aux Pwr Standby 50 mA mA
Alarm: 70 mA mA
SLC Standby 2.3 mA mA
Alarm: 40 mA mA
SLC Accessories
B200SR/-W/-IV Sounder Base Aux Pwr Standby: 0.5 mA mA
Alarm: 35 mA mA
SLC Standby 0.3 mA mA
B200S/-W/-IV Intelligent Sounder
Base
Aux Pwr Standby: 0.5 mA mA
Alarm: (high vol) 35 mA mA
SLC Standby 0.3 mA mA
B200SR-LF/-W/-IV Low Frequency
Sounder Base
Aux Pwr Standby: 1 mA mA
Alarm: 125 mA mA
B200S-LF/-W/-IV Low Frequency
Sounder Base
Aux Pwr Standby 0.55 mA mA
Alarm (high vol) 140 mA mA
SLC Standby 0.30 mA mA
B224RB/-W/-IV Relay Base Standby/Alarm: 0.17 mA mA mA
RTS151 Alarm: 10 mA
mA
RTS151KEY Alarm: 12 mA
mA
RA100Z Alarm: 10 mA
mA
SLC Isolator Devices
Device # of Devices Current per Device
Standby
Current
Alarm Current
Table 2.4 Current Draw Worksheet for SK SLC Devices