16 5895XL Manual — P/N 151142-L8:M 2/15/2022
Before You Begin Installing Calculating Current Draw and Standby Battery
2.5.3 Current Draw Worksheet for SD SLC Devices
For each 5895XL in the installation, use this worksheet in Table 2.5 to determine current requirements during alarm/battery standby opera-
tion. See individual FACP manual for maximum number of devices.
SK-FML Fiber Optic Multi Mode Standby/Alarm: 53 mA mA mA
SK-FSL Fiber Optic Single Mode Standby/Alarm: 79 mA mA mA
Wireless Modules
WSK-WGI Wireless Gateway Max current using ext supply 40 mA mA mA
Max current SLC Power 24 mA mA mA
A Total System Current
Auxiliary Devices Refer to devices manual for current rating
IPDACT-2 IP Communicator Standby: 93 mA mA
Alarm: 136 mA mA
IPDACT-2UD IP Communicator Standby: 98 mA mA
Alarm: 155 mA mA
CELL-MOD/CELL-CAB-SK Standby: 55 mA mA
Alarm: 100 mA mA
HWF2-COM Series Standby: 210 mA mA
Alarm: 290 mA mA
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
B Auxiliary Devices Current
4
Notification Devices Refer to device manual for current rating
5495/5499 Power Supply Standby: 75 mA
mA
Alarm: 205 mA
mA
Alarm: mA
mA
Alarm: mA
mA
Alarm: mA
mA
C Notification Appliances Current
mA
D Total current ratings of all devices in system (line A + line B + C) mA mA
E Total current ratings converted to amperes (line D x 0.001): A A
F Number of standby hours H
G Multiply lines E and F. Total standby AH AH
H Alarm sounding period in hours. (For example, 5 minutes = 0.0833 hours) H
I Multiply lines E and H. Total alarm AH
AH
J Add lines G and I. Total ampere hours
required
5
AH
1 The FACP can only support 5 devices with LEDs on. The current draw has been added to the panels alarm current.
2 The SK-BEAM-T draws a maximum of 500mA from auxiliary power when the test feature is used. This should be considered when
determining auxiliary power capacity but not calculated into current requirements for everyday operation.
3 Maximum SBUS address capacity is determined by the amount of SBUS bandwidth consumed by each SBUS module. Refer to the FACP
manual for SBUS limitations.
4 If there are door holders in the system, there is no need to consider door holder current for alarm/battery standby, because power is
removed during that time. However, during normal operation, door holders draw current and must be included in the 1.8 A total current that
can be drawn from the panel.
5 Use next size battery with capacity greater than required.
Device # of Devices Current per Device
Standby
Current
Alarm Current
Table 2.4 Current Draw Worksheet for SK SLC Devices
Device # of Devices Current per Device
Standby
Current
Alarm Current
For each device use this formula: This column X This column = Current per number of devices.
Table 2.5 Current Draw Worksheet for SD SLC Devices