5895XL Manual — P/N 151142-L8:M 2/15/2022 25
Battery Connection Installation
3.5 Battery Connection
The 5895XL battery charge capacity is 7 to 33 AH. Use 12V batteries of the same AH rating. Determine the correct AH rating as per the cur-
rent load calculation (see Table 2.4 or Table 2.5).
Wire batteries in series to produce a 24-volt equivalent. Do not parallel batteries to increase the AH rating.
3.6 Connecting the 5895XL to the FACP
1. Connect the 5895XL to the appropriate SBUS. The 5895XL can be connected directly to the FACP or it can be daisy-chained to another
5895XL. Refer to Figures 3.5 and 3.6.
2. Use the onboard DIP switch to assign an ID number. (See Section 3.6.1) Figure 2.1 shows the location of the DIP switches on the
5895XL board.
3. Add the 5895XL module to the system and configure the module using JumpStart auto-programming or by manually entering
information into the FACP.
It is possible to assign a name to the module. These procedures are described in the FACP Installation Manuals. Refer to Table 1.1.
.
NOTE: If the backup battery requirements indicate the use of batteries that are too large to fit into the 5895XL cabinet, use the RBB Remote
Battery Box cabinet. Refer to the RBB Installation Instructions #151306.
_
_
+
+
Battery Jumper
(P/N 140694)
Replace batteries every five years.
to panel
Figure 3.4 Battery Connection
5895XL Terminals 30-33 are used only for connection
5895XL to the FACP or to the controlling 5895XL.
Use 5895XL Terminals 16-19 to connect other SBUS
modules (SLC expanders, annunciators, 5824) and to
daisy-chain 5895XL modules.
5895XL Board
(5895XL-1)
To next 5895XL and
other SBUS modules
5895XL Board
(5895XL-2)
Maximum wire length is 6,000 feet.
See Section 2.6 for more information.
FACP SBUS
Connect other SBUS modules here.
Figure 3.5 Class B 5895XL Connection to FACP