30 5895XL Manual — P/N 151142-L8:M  2/15/2022
Installation Flexput I/O Circuits
3.8.4  Installing 2-Wire Smoke Detectors
Any compatible UL listed two-wire smoke detector can be used with the 5895XL panel. Refer to the Device Compatibility Document for a 
list of compatible devices. Figure 3.14 and Figure 3.15 illustrate how to connect a UL listed 2-wire detector to the 5895XL panel.
Class B Installation
To install a Class B two-wire smoke detector, wire as shown in Figure 3.14.
Class A Smoke Detector Installation
To install a Class A two-wire smoke detector, wire as shown in Figure 3.15.
15 14
0X
I / 0  1
13 12
0X
I / 0  2
11 10
0X
I / 0  3
987654
0X0X0X
I / 0  4
I / 0  5 I / 0  6
L3+
S1-
L3+
S1-
Note: I/O circuit 5 is used 
as an example. Any I/O 
point pairing can be used.
UL listed EOL
4.7 kΩ
Figure 3.14  Two-Wire Class B Smoke Detector
15 14
0X
I / 0  1
13 12
0X
I / 0  2
11 10
0X
I / 0  3
987654
0X0X0X
I / 0  4
I / 0  5 I / 0  6
point pairs
Note: I/O circuit 5 and 6 are 
used as an example. Any I/O 
point pairing can be used.
Figure 3.15  Two-Wire Class A Smoke Detector Connections
NOTE: In programming, any point that uses multiple I/O circuits are always referred to as the lowest I/O circuit number used. For example, 
since Figure 3.15 uses both I/O circuit 5 and 6, it would be referred to as point 5.