30 5895XL Manual — P/N 151142-L8:M 2/15/2022
Installation Flexput I/O Circuits
3.8.4 Installing 2-Wire Smoke Detectors
Any compatible UL listed two-wire smoke detector can be used with the 5895XL panel. Refer to the Device Compatibility Document for a
list of compatible devices. Figure 3.14 and Figure 3.15 illustrate how to connect a UL listed 2-wire detector to the 5895XL panel.
Class B Installation
To install a Class B two-wire smoke detector, wire as shown in Figure 3.14.
Class A Smoke Detector Installation
To install a Class A two-wire smoke detector, wire as shown in Figure 3.15.
15 14
0X
I / 0 1
13 12
0X
I / 0 2
11 10
0X
I / 0 3
987654
0X0X0X
I / 0 4
I / 0 5 I / 0 6
L3+
S1-
L3+
S1-
Note: I/O circuit 5 is used
as an example. Any I/O
point pairing can be used.
UL listed EOL
4.7 kΩ
Figure 3.14 Two-Wire Class B Smoke Detector
L3+
S1-
L3+
S1-
L3+
S1-
15 14
0X
I / 0 1
13 12
0X
I / 0 2
11 10
0X
I / 0 3
987654
0X0X0X
I / 0 4
I / 0 5 I / 0 6
point pairs
Note: I/O circuit 5 and 6 are
used as an example. Any I/O
point pairing can be used.
Figure 3.15 Two-Wire Class A Smoke Detector Connections
NOTE: In programming, any point that uses multiple I/O circuits are always referred to as the lowest I/O circuit number used. For example,
since Figure 3.15 uses both I/O circuit 5 and 6, it would be referred to as point 5.