EasyManua.ls Logo

Honeywell Silent knight 5895XL - 3: Conventional Initiation Circuits; Class B Inputs; Class a Inputs

Honeywell Silent knight 5895XL
34 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
5895XL Manual — P/N 151142-L8:M 2/15/2022 29
Flexput I/O Circuits Installation
3.8.3 Conventional Initiation Circuits
This Section of the manual explains how to install the conventional initiating devices for Class A or Class B configurations.
Class B Inputs
Connect conventional Class B switches, such as waterflow switches and pull stations, directly to the I/O circuits of the 5895XL panel.
To install a Class B switch, wire the switch as shown in Figure 3.12 and configure the circuit through FACP programming.
Class A Inputs
Connect conventional Class A switches, such as waterflow switches and pull stations, directly to the I/O circuits of the 5895XL panel.
To install a Class A switch, wire the switch as shown in Figure 3.13 and configure the circuit through FACP programming.
15 14
0X
I / 0 1
13 12
0X
I / 0 2
11 10
0X
I / 0 3
987654
0X0X0X
I / 0 4
I / 0 5 I / 0 6
UL listed EOL
4.7 kΩ
Figure 3.12 Class B Input Switches
15 14
0X
I / 0 1
13 12
0X
I / 0 2
11 10
0X
I / 0 3
987654
0X0X0X
I / 0 4
I / 0 5 I / 0 6
point pairs
Note: I/O circuit 5 and 6 are
used as an example. Any I/O
point pairing can be used.
Figure 3.13 Class A Initiating Switches
NOTE: In programming, any point that uses the multiple I/O circuits are always referred to as the lowest I/O circuit number used. For example,
since Figure 3.13 uses both I/O circuit 5 and 6, it would be referred to as point 5.

Table of Contents

Other manuals for Honeywell Silent knight 5895XL

Related product manuals