Calculating Current Draw and Standby Battery Before You Begin Installing
SK-ISO (Isolator Module) Standby: 0.45 mA mA mA
Isolation: 17 mA
ISO-6 (6 Fault Isolator Module) Standby: (per circuit) 0.45 mA mA
Isolation: (per circuit) 17 mA mA
B224BI/-W/-IV Isolator Base Standby: 0.45 mA mA
Isolation: 15 mA mA
Accessories Modules
3
6815 SLC Loop Expander Standby: 78 mA mA
Alarm: 78 mA mA
6860 Remote LCD Annunciator Standby: 27 mA mA
Alarm: 53 mA mA
5860 Remote LCD Annunciator Standby: 58 mA mA
Alarm: 68 mA mA
6855 Remote LCD Annunciator Standby: 59 mA mA
Alarm: 92 mA mA
5824 Serial/Parallel Module Standby/Alarm: 45 mA mA mA
5496 NAC Expander Standby/Alarm (SBUS): 10 mA mA mA
5895XL Power Supply Standby/Alarm (SBUS): 10 mA mA mA
5865-4 LED Annunciator
(with reset and silence switches)
Standby: 35 mA mA
Alarm: 145 mA mA
5865-3 LED Annunciator Module Standby: 35 mA mA
Alarm: 145 mA mA
5880 LED I/O Module Standby: 35 mA mA
Alarm: 200 mA mA
5883 Relay Interface Standby: 0 mA mA
Alarm: (22 mA/relay) 220 mA mA
EVS-50W Voice Amplifier
with/without EVS-CE4
Standby/Alarm (SBUS): 10 mA mA mA
EVS-125W Voice Amplifier
with/without EVS-CE4
Standby/Alarm (SBUS): 10 mA mA mA
EVS-INT50W Internal Amplifier Standby: 52 mA mA
Alarm @ 25V: 275 mA mA
Alarm @ 70V: 310 mA
mA
EVS-100W Amplifier Standby/Alarm (SBUS): 10 mA mA mA
EVS-100WBU Back-Up Amplifier Standby/Alarm: 10 mA mA mA
EVS-VCM Voice Control Module Standby: 70 mA mA
Alarm: 100 mA mA
EVS-NVCM Voice Control Module Standby/Alarm: 59 mA mA mA
EVS-RVM Remote Voice Module Standby: 60 mA
Alarm: 80 mA
EVS-SW24 Switch Expander Standby: 10 mA mA
Alarm: 25 mA mA
EVS-RPU Remote Paging Unit Standby: 70 mA mA
Alarm: 100 mA mA
EVS-LOC Local Operating Console Standby: 87 mA mA
Alarm: 133 mA mA
EVS-LOC Local Operating Console
with one EVS-SW24
Standby: 97 mA mA
Alarm: 158 mA mA
Network Cards
SK-NIC Network Interface Card Standby/Alarm: 21 mA mA mA