18 5895XL Manual — P/N 151142-L8:M 2/15/2022
Before You Begin Installing Calculating Current Draw and Standby Battery
5880 LED I/O Module Standby: 35 mA mA
Alarm: 200 mA mA
5883 Relay Interface Standby: 0 mA mA
Alarm: (22 mA/relay) 220 mA mA
EVS-50W Voice Amplifier
with/without EVS-CE4
Standby/Alarm (SBUS): 10 mA mA mA
EVS-125W Voice Amplifier
with/without EVS-CE4
Standby/Alarm (SBUS): 10 mA mA mA
EVS-INT50W Internal Amplifier Standby: 52 mA mA
Alarm @ 25V: 275 mA mA
Alarm @ 70V: 310 mA
mA
EVS-100W Amplifier Standby/Alarm (SBUS): 10 mA mA mA
EVS-100WBU Back-Up Amplifier Standby/Alarm: 10 mA mA mA
EVS-VCM Voice Control Module Standby: 70 mA mA
Alarm: 100 mA mA
EVS-NVCM Voice Control
Module
Standby/Alarm: 59 mA mA mA
EVS-RVM Remote Voice Module Standby: 60 mA
Alarm: 80 mA
EVS-SW24 Switch Expander Standby: 10 mA mA
Alarm: 25 mA mA
EVS-RPU Remote Paging Unit Standby: 70 mA mA
Alarm: 100 mA mA
EVS-LOC Local Operating
Console
Standby: 87 mA mA
Alarm: 133 mA mA
EVS-LOC Local Operating
Console with one EVS-SW24
Standby: 97 mA mA
Alarm: 158 mA mA
Network Cards
SK-NIC Network Interface Card Standby/Alarm: 21 mA mA mA
SK-FML Fiber Optic Multi Mode Standby/Alarm: 53 mA mA mA
SK-FSL Fiber Optic Single Mode Standby/Alarm: 79 mA mA mA
Wireless Modules
WSK-WGI Wireless Gateway Max current using ext supply 40 mA mA mA
Max current SLC Power 24 mA mA mA
A Total System Current
Auxiliary Devices
2
Refer to devices manual for current rating
IPDACT-2 IP Communicator Standby: 93 mA mA
Alarm: 136 mA mA
IPDACT-2UD IP Communicator Standby: 98 mA mA
Alarm: 155 mA mA
CELL-MOD/CELL-CAB-SK Standby: 55 mA mA
Alarm: 100 mA mA
HWF2-COM Series Standby: 210 mA mA
Alarm: 290 mA mA
Alarm/Standby: mA mA mA
Alarm/Standby: mA mA mA
B Auxiliary Devices Current
4
Notification Devices Refer to device manual for current rating
5495/5499 Power Supply Standby: 75 mA
mA
Alarm: 205 mA
mA
Device # of Devices Current per Device
Standby
Current
Alarm Current
Table 2.5 Current Draw Worksheet for SD SLC Devices