Revision 4  Foundation Fieldbus RMA803 Remote Indicator User's Guide  Page 43 
Parameter  Description 
WRITE_ALM  This alert is generated if the write lock parameter is cleared. 
ITK_VER  Major revision number of the interoperability test case used in certifying this 
device as interoperable. The format and range are controlled by the 
Fieldbus Foundation. The current ITK version is 6.0.1. 
FD_VER  A parameter equal to the value of the major version of the Field Diagnostics 
specification that the device is designed for. 
FD_RECOMMEN_AC
T 
Enumerated list of recommended actions displayed with a device alert. 
FD_FAIL_PRI  Designates the alarming priority of the FAIL_ALM. The valid range is 0-15. 
FD_FAIL_MAP  Mapped FAIL_ALM alarm conditions, and corresponds bit for bit to the 
FAIL_ACTIVE. A bit on means that the corresponding alarm condition is 
Mapped and it is detected. A bit off means the corresponding alarm 
condition is disabled and is not detected. 
FD_FAIL_MASK  Mask of FAIL_ALM. It corresponds to the bit of bit to FAIL_ACTIVE. A bit on 
means that the condition is masked out from alarming. 
FD_FAIL_ACTIVE  Enumerated list of failure conditions within a device. 
FD_FAIL_ALM  Alarm indicating a failure within a device which makes the device non-
operational. 
FD_MAINT_PRI  Designates the alarming priority of the MAINT_ALM. The valid range is 0-
15. 
FD_MAINT_MAP  Mapped MAINT_ALM alarm conditions and corresponds bit for bit to the 
MAINT_ACTIVE. A bit on means that the corresponding alarm condition is 
Mapped and is not detected. A bit off means the corresponding alarm 
condition is disabled and is not detected. 
FD_MAINT_MASK  Mask of MAINT_ALM. It corresponds to the bit of bit to MAINT_ACTIVE. A 
bit on means that the condition is masked out from alarming. 
FD_MAINT_ACTIVE  Enumerated list of maintenance conditions within a device. 
FD_MAINT_ALM  Alarm indicating the device needs maintenance soon. If the condition is 
ignored, the device eventually fails. 
FD_OFFSPEC_PRI  Designates the alarming priority of the OFFSPEC_ALM. The valid range is 
0-15. 
FD_OFFSPEC_MAP  Mapped OFFSPEC_ALM alarm conditions. Corresponds bit for bit to the 
OFFSPEC_ACTIVE. A bit on implies that the corresponding alarm condition 
is Mapped and detected. A bit off means the corresponding alarm condition 
is disabled and is not detected. 
FD_OFFSPEC_MAS
K 
Mask of OFFSPEC_ALM. It corresponds to the bit of bit to 
OFFSPEC_ACTIVE. A bit on implies that the condition is masked out from 
alarming. 
FD_OFFSPEC_ACTI
VE 
Enumerated list of offspec conditions within a device. 
FD_OFFSPEC_ALM  Alarm indicating offspec alarms. These conditions do not have a direct 
impact on the process or device integrity. 
FD_CHECK_PRI  Designates the alarming priority of the CHECK_ALM. The valid range is 0-
15.