Revision 2.0 FOUNDATION Fieldbus ST 700 Pressure Transmitter User's Guide Page 31
Parameter Description
SENSOR_ISOLATOR_MTL Defines the construction material for the isolating diaphragms.
SENSOR_TYPE The type of sensor connected with the transducer block.
SENSOR_RANGE The high and low range limit values, the engineering units code, and the
number of digits to the right of the decimal point for the sensor.
SENSOR_SN The sensor serial number.
SENSOR_CAL_METHOD The method of last sensor calibration.
SENSOR_CAL_LOC The location of the last sensor calibration. This describes the physical
location at which the calibration was performed.
SENSOR_CAL_DATE The date of the last sensor calibration. It shows the calibration of that part
of the sensor that is usually wetted by the process.
SENSOR_CAL_WHO The name of the person who did the last sensor calibration.
SENSOR_FILL_FLUID It defines the type of fill fluid used in the sensor.
SECONDARY_VALUE The secondary value that is related to the sensor.
SECONDARY_VALUE_UNIT The engineering unit to be used with the SECONDARY_VALUE.
SECONDARY_VALUE_TYPE The type of measurement represented by the Secondary value. For
example, Pressure, Temperature.
SECONDARY_VALUE_UPPE
R_RANGE
The High range limit value of the Secondary value.
SECONDARY_VALUE_LOW
ER_RANGE
The Low range limit value of the Secondary value.
TERTIARY_VALUE The measured value and status available to the function block.
TERTIARY_VALUE_UNIT The engineering units code of the Tertiary value.
TERTIARY_VALUE_TYPE The type of measurement represented by the Tertiary value. For Example:
Pressure, Temperature.
TERTIARY_VALUE_UPPER_
RANGE
The High ranges limit value of the Tertiary value.
TERTIARY_VALUE_LOWER_
RANGE
The Low range limits value of the Tertiary value.
EL_TEMPERATURE The value and status of the measured temperature inside the electronics
housing.
EL_TEMP_UNIT The engineering units code used to display the Electronics Temperature.
CAL_STATUS The current status of the last performed calibration.
QUATENARY_VALUE The value and status of the fluid level calculated as a polynomial of
differential pressure.
TANK_RANGE Tank Range scaling: It contains the upper and lower range of pressure
measurement of a tank. It is used primarily in level applications
specifically for the polynomial calculation.