PLUMBING
STEP THREE: Connect Steam Humidier to the Cold Water Pipe
Connect one end of the remaining length of water
line to the backow preventer. Apply a modest pull
to ensure a tight t. See “Reverse Osmosis Filter” on
page 24 if using the Reverse Osmosis Filter.
Connect the other end of this line to the saddle valve
or T-tting and manual shutoff valve.
STEP FOUR: Connect to the Water Drain
• Consult and follow local plumbing codes for drain
pipe size and maximum temperature requirement.
• The ideal installation is directly to the main oor
drain using the rubber hose provided.
• If direct oor drain access is not available, see
“Other Plumbing Options” on page 16.
Connect the 1/2-inch drain hose provided to the drain
tting on the bottom of the steam humidier.
Use the hose clamp provided to secure the drain hose
to the barbed tting.
Route the drain hose to the oor drain. The hose must
have a continuous downward slope.
Direct the hose outlet into the oor drain. Secure
the hose to reduce the risk of hot water pooling
or splashing.
Note: Some building codes require an air gap between
discharge hose and oor drain.
MCR29607
Before proceeding to Wiring:
I have conrmed minimum required circuit capacity
I have connected the water supply using cold water
I have installed the drain connection
CAUTION: Scalding Hazard.
During operation, hot water may exit drain and can cause burns from scalding.
Make sure the hose is securely connected to the drain.
Steam Humidier System 69-2285—09 15
2
1
3
2
1
4