OPERATION
AND SERVICE
Steam Humidier System 69-2285—09
50
No. of
Service LED
Blinks
Fault Description Auto-Recoverable? Steps to Fix
(Performed Only By Professional HVAC Technician)
1 Water Heater
temperature sensor is
out of range.
Yes, steam
humidier will reset
if fault no longer
exists in one hour.
1. Unplug steam humidier & remove cover
2. Check Water sensor connection to board. Remove and plug
back in.
3. Press the Go button.
4. If fault returns, replace steam humidier
2 Water sensors failed. Yes, steam
humidier will reset
if fault no longer
exists in one hour.
1. Unplug steam humidier and remove cover.
2. Disconnect water level sensor wiring.
3. Ohm out water sensor
4. Readings between P1 & P3, P1 & P4, P2 & P4 and P4 & P5
should all show innite resistance. If they do not replace the
sensor.
3 Failure to ll tank
with water.
Yes, system will
return to “Ready”
if fault no longer
exists in
three hours.
1. Ensure inlet water is on.
2. Check for voltage on the ll terminals for the solenoid valve
(should be appox. 120vac)
3. Check for leaks around the tank seal and solenoid.
4. If using an RO lter make sure the ush timer is set for 30
hours
5. If using an RO lter, follow troubleshooting information as
outlined in RO install guide.
6. If not using an RO lter, turn off water supply and replace any
in line water lter.
7. Press and hold the go button until res Service light turns off.
8. If tank still fails to ll, press the Drain button.
9. If tank fails to drain, unplug steam humidier (and make sure
water in tank is cool before proceeding).
10. Follow the tank cleaning steps.
11. Ensure you have a rm grip on the tank before releasing the
tank, especially if water is present.
12. Clear any excess debris from the tank’s bottom orice to the
solenoid.
13. Reassemble tank and plug steam humidier back in. Press the
button to reset. If water still fails to ll into the tank, replace the
solenoid valve
Steam Humidier has internal system diagnostics that monitor operation, maintenance schedules, and faults. If a
system fault is detected, Steam Humidier will attempt to recover up to ve times in a 24-hour period.
• If Steam Humidier is unable to recover by itself within 24 hours, the red Service light blinks in a series that
indicates the fault detected.
• Refer to the table below for the fault indicated, along with the steps to x Steam Humidier.
• Press and hold the Go button until the Service light turns off.
Troubleshooting