EasyManua.ls Logo

Honeywell Steam Humidifier - Page 44

Honeywell Steam Humidifier
72 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
WIRING
Honeywell HumidPRO
TM
Frost Index
Installer System Test/Checkout
Outdoor Temp
-10°F 0°F 10°F 20°F 30°F 40°F
Frost Index
1 10 10 10 10 11 11 17 17 25 25 35 36
2 10 10 10 10 15 15 21 21 29 29 35 39
3 10 10 14 14 19 19 26 26 34 34 35 46
4 15 15 19 19 25 25 32 32 35 39 35 52
5 21 21 26 26 32 32 35 38 35 48 35 58
6 29 29 34 34 35 39 35 48 35 56 35 60
7 35 39 35 46 35 52 35 58 35 60 35 60
8* 35 56 35 60 35 60 35 60 35 60 35 60
9 35 60 35 60 35 60 35 60 35 60 35 60
10 35 60 35 60 35 60 35 60 35 60 35 60
*Black Numbers show highest humidity allowed when Default RH% (35%) is Selected.
Note: Smaller grey numbers show highest humidity allowed when Maximum RH% (60%) is selected.
Press p / q to turn system on/off.
Press NEXT to advance to next test.
Press DONE to terminate system test.
To begin, press and hold the p and q buttons until the display changes.
Function Number
Setting
Number Description
10 System Test
0 OFF
1 ON
20 View Outdoor Temperature
Shows Outdoor Temperature
10
0
M29388A
Test number System status
NOTE: Most humidiers require airow in the system to operate. Make sure to turn on the system fan when
testing humidier operation.
H6062 Specications
Humidity Ranges:
Humidify:
Default: 10% to 60%
Total Range Available: 10% to 90%
Operating Ambient Temperature
32° to 120°F (0° to 48.9°C)
Operating Relative Humidity
5% to 90% (non-condensing)
Steam Humidier System 69-2285—09
42

Table of Contents

Related product manuals