TB3 SERIES COMMUNICATING THERMOSTATS INSTALLATION INSTRUCTIONS
17 31-00576-01
7
Analog
Value #7
0 to 2
Power
Failure
This parameter adjusts the
device's condition to
continue when the power
fails.
0 = Device starts off
1 = Device starts on
2 = Keep State Before
Power Failure
2 R/W -
8
Analog
Value #8
2 to 4
Fan Coil
Type
2 = 2 Pipe System
4 = 4 Pipe System
4 R/W -
9
Analog
Value #9
-10 °C to 0 °C
(-18 °F to 18 °F)
Internal
Temperature
Sensor
Calibration
This parameter adjusts
sensor value calibrate with
0.1 °C (1°F) steps.
0 °C (0 °F) R/W -
10
Analog
Value #10
0 to 5
Universal
Input
0 = Not Used
1=External temperature
sensor for the room (NTC
10K)
2 = External temperature
sensor (NTC 10K)
3 = Changeover sensor
(NTC 10K)
4 = Windows
contact/Energy saving-
On/Off (NC Contact)
5 = Windows
contact/Energy saving-
Off/On (NO Contact)
0 R/W COV
11
Analog
Value #11
10 °C to 25 °C
(50 °F to 77 °F)
Changeover
Temperature
for Cooling
If “Universal Input” is set to
“3”, this parameter adjusts
the changeover
temperature for cooling
mode.
16 °C
(61 °F)
R/W -
12
Analog
Value #12
26 °C to 45 °C
(79 °F to 113 °
F)
Changeover
Temperature
for Heating
If “Universal Input” is set to
“3”, this parameter adjusts
the changeover
temperature for heating
mode.
28 °C
(82 °F)
R/W -
13
Analog
Value #13
0 to 255
minutes
Mode
Change
Delay
This parameter adjusts the
delay time between the
heat and cool modes.
3 minutes R/W -
14
Analog
Value #14
-10 °C …10 °C
(-18 °F…18 °F)
Universal
Input
Temperature
Calibration
This parameter adjusts
sensor value calibrate with
0.1 °C (1°F) steps.
0 °C R/W -
15
Analog
Value #15
0 °C…15 °C
(0 °F…27 °F)
Dead Zone
If “Mode” is set to “Auto”,
this parameter adjusts the
dead zone.
2 °C (4 °F) R/W -
16
Analog
Value #16
0 °C…15 °C
(0 °F…27 °F)
Hysteresis
This parameter adjusts the
hysteresis.
1 °C (2 °F) R/W -
17
Analog
Value #17
0 to 5 second
Fan Stage
Change
Delay
This parameter adjusts the
delay of the changing
range of the fan.
2 second R/W -
18
Analog
Value #18
0 to 60 second
Fan Off
Delay
This parameter adjusts the
delay of the closing time of
the fan.
0 second R/W -
NO OBJECT VALUE
OBJECT
NAME
FUNCTION DEFAULT
READ (R)/
WRITE (W)
COV
PROPERTY