SETUP TB6575/TB8575 SUITEPRO™ DIGITAL FAN COIL THERMOSTATS
11 62-0278—01
11 CPH Value
for Heat
1 to 12 Range is 1 to 12. Default is 4. The number selected indicates the
maximum times Heating is cycled on
per hour (CPH).
12 CPH Value
for Cool
1 to 6 Range is 1 to 6. Default is 3. The number selected indicates the
maximum times Cooling is cycled on
per hour (CPH).
13 CPH for
Auxiliary
Electrical
Heater
1 to 12 Range is 1 to 12. Default is 6. The number selected indicates the
maximum times Auxiliary Heating is
cycled on per hour (CPH).
14 Display
Temperature
Adjustment
-4 to 4 Range is -4°F to +4°F; Default is 0°F.
15 Temperature
Display
Mode
0 Display Room Temperature
1 Display Setpoint
2 Display Temperature and Setpoint; Default.
16 Setpoint
Range Stop
for Heating
50 to 90 Range is 50°F to 90°F. Default is 90°F.
17 Setpoint
Range Stop
for Cooling
50 to 90 Range is 50°F to 90°F. Default is 50°F.
18 Keypad
Lockout
0 All keys are available; Default
1 The System button (Heat/Cool) is locked out
2 Both the System and Fan buttons are locked out.
3 All buttons are locked out (System, Fan, Up Arrow, and Down
Arrow). The LCD displays LOCKeD.
19 Remote
Setback
0 Disabled; Default
1 Hotel card enabled N.O. with
1 second software delay going from UnOccupied to Occupied;
2 minute delay going from Occupied to UnOccupied.
2 Hotel Card enabled N.C. with
1 second software delay going from UnOccupied to Occupied;
2 minute delay going from Occupied to UnOccupied.
3 Hotel Card enabled N.O. with
1 second software delay going from UnOccupied to Occupied;
30 minute delay going from Occupied to UnOccupied
4 Hotel Card enabled N.C. with
1 second software delay going from UnOccupied to Occupied;
30 minute delay going from Occupied to UnOccupied.
20 Remote
Setback for
Heating
50 to 70 Range is 50°F to 70°F. Default is 64°F. Used when the thermostat is in the
Unoccupied state.
21 Remote
Setback for
Cooling
72 to 90 Range is 72°F to 90°F. Default is 79°F.
22 Activity
Sensing
0 Disabled; Default Anytime the thermostat is not
touched (no single key is pressed) for
the duration selected, the thermostat
automatically falls back into the
Unoccupied setpoints. When any key
is pressed, the thermostat controls to
Occupied mode
NOTE: IS code #19 (Remote Set-
back) must be disabled
(value = 0) in order to dis-
play the Activity Sensing
code.
1 4 hour sensing
2 12 hour sensing
3 24 hour sensing
Table 4. Installer Setup (IS) Codes and Options. (Continued)
IS
Code
Code
Description
Option
Value Option Description (Default value shown in Bold) Notes