37 TR80 - Installation and Operation Guide
An override cancellation occurs when a bit is set (on a change from 0 to 1). The wall module
takes no action when a bit is cleared.
3. 4. 3 What has changed
This register changes when the user makes any adjustment on the wall module. It can be uti-
lized by a master controller to reduce comms. It will be sufficient for the controller to read only
this register until a non-zero value is received. Then, and only then, the controller would need
to read the new user setting from the relevant register.
It is important to note that this register automatically returns to the default value of 0 as soon
as it is read by the master controller. There is no need for the master to reset it.
3. 4. 4 Active Display Mode
This register allows monitoring of the current user mode.
Register
type
Relative
Address
Absolute
Address
Dir Name Type Range
Default
value
Input 9 30010 R What has changed bitwise
Bit0: Setpoint
Bit1: Fan speed
Bit2: HVAC mode
Bit3: {reserved}
Bit4: Occupancy
Bit5: DnD/Mur
Bit6: {reserved}
Bit7: Temperature unit
Bit8: Light group 1
Bit9: Light group 2
Bit10: Light group 3
Bit11: Light group 4
Bit12: Blind 1
Bit13: Blind 2
0
Register
type
Relative
Address
Absolute
Address
Dir Name Type Range
Input 100 30101 R
Active display
mode
enum
0: Dark mode
1: Sleep mode
2: Ready mode
3: Protected mode
4: Setting mode (temp, light etc)
5: Config mode
6: Cleaning mode
7: Pin entry