TR80 - Installation and Operation Guide 52
3. 11. 3 Light Group 2 configuration & control
The configuration parameter for group 2 are explained in below table. Refer lighting
group1 for explanation.
The group 2 control parameters are explained in below table. Refer lighting group1 for
explanation.
3. 11. 4 Light Group 3 configuration & control
The group 3 configuration parameters are explained in below table. Refer lighting group1
for explanation.
The group 3 control parameters are explained in below table. Refer lighting group1 for
explanation.
Register
type
Relative
Address
Absolute
Address
Dir Name
Config
Parameter
Unit Range
Default
value
Holding 2306 42307 R/W
Light Group 2
allow dimming
306 enum
0: only on/off
control
1: allow dimming
1
Holding 2307 42308 R/W
Light Group 2
min level
307 % 0…100% 1%
Holding 2308 42309 R/W
Light Group 2
max level
308 % 0…100% 100%
Holding 2309 42310 R/W
Light Group 2
max Scene No
309 int 0-16 4
Register
type
Relative
Address
Absolute
Address
Dir Name Unit Range
Default
value
Holding 1302 41303 R/W Light Group level feedback % 0-100%
32768
(invalid)
Holding 1303 41304 R/W Light Group last scene feedback int 0-15 0
Input 302 30303 R/W Light Group 2 new level % 0-100% 32767
Input 303 30304 R/W Light Group 2 new scene int 0-15 32767
Register
type
Relative
Address
Absolute
Address
Dir Name
Config
Parameter
Unit Range
Default
value
Holding 2310 42311 R/W Light Group 3 allow dimming 310
enu
m
0: only on/off
control
1: allow dimming
1
Holding 2311 42312 R/W Light Group 3 min level 311 % 0…100% 1%
Holding 2312 42313 R/W Light Group 3 max level 312 % 0…100% 100%
Holding 2313 42314 R/W Light Group 3 max Scene No 313 int 0-16 4
Register
type
Relative
Address
Absolute
Address
Dir Name Unit Range
Default
value
Holding 1304 41305 R/W Light Group level feedback % 0-100%
32768
(invalid)
Holding 1305 41306 R/W Light Group last scene feedback int 0-15 0
Input 304 30305 R/W Light Group 3 new level % 0-100% 32767
Input 305 30306 R/W Light Group 3 new scene int 0-15 32767