55 TR80 - Installation and Operation Guide
3. 12. 2 Blind Group 1 control parameters
‘Position Feedback’ and ‘Angle Feedback’ information typically come from the master control-
ler. When the user enters the setting mode for any blind, these are the values that will be dis-
played initially, and the user will start setting (incrementing / decrementing) from these
values.
The ‘New Position’ and ‘New Angle’ registers are used to convey user commands. These will
normally be at an invalid value of 32767. If the user adjusts the position or angle on the wall
module, the relevant register will contain the newly set value. But as soon as it is read over
Modbus, it will automatically revert to the invalid value of 32767. This scheme ensures all user
commands are registered as a change-of-value and can be acted upon by the master control-
ler.
3. 12. 3 Blind Group2 Configuration & Control Parameters
The Blind 2 configuration parameters are as shown below.
The Blind 2 control parameters are as shown below.
Register
type
Relative
Address
Absolute
Address
Dir Name Unit Range
Default
value
Holding 1400 41401 R/W Blind 1 position feedback % 0-100% 50%
Holding 1401 41402 R/W Blind 1 angle feedback ° -180…+180° 0
Input 400 30401 R/W Blind 1 new position % 0-100% 32767
Input 401 30402 R/W Blind 1 new angle ° -180…+180° 32767
Register
type
Relative
Address
Absolute
Address
Dir Name
Config
parameter
Unit Range
Default
value
Holding 2408 42409 R/W Blind 2 type 408 bitwise
Bit 0: angle control
Bit 1: position direct/
reverse
1
Holding 2409 42410 R/W
Blind 2 min
pos
409 % 0…100% 0%
Holding 2410 42411 R/W
Blind 2 max
pos
410 % 0…100% 100%
Holding 2411 42412 R/W
Blind 2 min
angle
411 ° -180°…180° -80°
Holding 2412 42413 R/W
Blind 2 max
angle
412 ° -180°…180° +80°
Register
type
Relative
Address
Absolute
Address
Dir Name Unit Range
Default
value
Holding 1402 41403 R/W Blind 2 position feedback % 0-100% 50%
Holding 1403 41404 R/W Blind 2 angle feedback ° -180…+180° 0
Input 402 30403 R/W Blind 2 new position % 0-100% 32767
Input 403 30404 R/W Blind 2 new angle ° -180…+180° 32767