2.3  Control and Alarm Relay Contact Information 
Control Relays 
ATTENTION
Control relays operate in the standard control mode (that is, energized when output state is on). 
Table 2-1  Control Relay Contact Information 
Unit Power  Control Relay  
Wiring
Control Relay  
Contact
Output #1 or #2 
Indicator Status 
N.O.  Open 
Off
N.C.  Closed 
Off
Open
Off
N.O.
Closed
On
Closed
Off
On
N.C.
Open
On
Alarm Relays 
ATTENTION
Alarm relays are designed to operate in a failsafe mode (that is, de-energized during alarm 
sate). This results in alarm actuation when power is OFF or when initially applied, until the unit 
completes self-diagnostics. If power is lost to the unit, the alarms will de-energize and thus the 
alarm contacts will close. 
Table 2-2  Alarm Relay Contact Information 
Variable NOT in Alarm State  Variable in Alarm State Unit
Power 
Alarm Relay 
Wiring
Relay  
Contact
Indicators Relay  
Contact
Indicators
N.O.  Open  Open 
Off
N.C.  Closed 
Off
Closed
Off
N.O.  Closed  Open 
On
N.C. Open
Off
Closed
On