UNIPOINT OPERATING MANUAL 2306M5001 MAN0638 ISSUE 7 01/2011
10
5 Default Conguration
Unipoint has user congurable settings that allow the set up of the system to individual
application requirements. Unipoint is supplied from the factory with a default conguration.
These congurations are based on settings typically used in gas detection systems.
Details of how to recongure Unipoint are given in section 7.
5.1 Unipoint mV Input Version
Function Default conguration
Password 000 (Disabled)
Display range and units 0-100%LEL
Alarm Relay 1 Alarm level 1 10%LEL (Rising)
Non-latching, normally de energized, energizes on alarm.
Relay activation delay=0 seconds
Relay de-activation hold=0 seconds
(Single Pole change over, 240Vac/30Vdc, 3A max)
Alarm Relay 2 Alarm level 2 25%LEL (Rising)
Non-latching, normally de energized, energizes on alarm.
Relay activation delay=0 seconds
Relay de-activation hold=0 seconds
(Single Pole change over, 240Vac/30Vdc, 3A max)
Alarm Relay 3 Alarm level 3 50%LEL (Rising)
Latching, normally de energized, energizes on alarm.
Relay activation delay=0 seconds
Relay de-activation hold=0 seconds
(Single Pole change over, 240Vac/30Vdc, 3A max)
Fault Relay Non-latching, normally energized, de-energizes on fault.
(Single Pole change over, 240Vac/30Vdc, 3A max)
Inhibit Controller inhibit activates fault relay.
5.2 Unipoint 4-20mA Input Version
Function Default conguration
Password 000 (Disabled)
Display range and units 0-100ppm
Current input 0 mA Fault (open circuit)
4.0 to 20.0mA Gas reading (normal operation)
1.5 to 2.5mA Inhibit from sensor (configuration mode)
>20.0mA Overrange
Alarm Relay 1 Alarm level 1 10% of full scale (Rising)
Non-latching, normally de energized, energizes on alarm.
Relay activation delay=0 seconds
Relay de-activation hold=0 seconds
(Single Pole change over, 240Vac/30Vdc, 3A max)
Alarm Relay 2 Alarm level 2 25% of full scale (Rising)
Non-latching, normally de energized, energizes on alarm.
Relay activation delay=0 seconds
Relay de-activation hold=0 seconds
(Single Pole change over, 240Vac/30Vdc, 3A max)
Alarm Relay 3 Alarm level 3 50%LEL (Rising)
Latching, normally de energized, energizes on alarm.
Relay activation delay=0 seconds
Relay de-activation hold=0 seconds
(Single Pole change over, 240Vac/30Vdc, 3A max)
Fault Relay Non-latching, normally energized, de-energizes on fault.
(Single Pole change over, 240Vac/30Vdc, 3A max)
Inhibit Controller inhibit activates fault relay and de-activates alarm relays.
Field inhibit active (1.5 to 2.5mA on detector input).
Detector Type 2 Wire 4-20mA