EasyManua.ls Logo

Honeywell Unitary Series - Input; Output Wiring; Wiring Requirements

Honeywell Unitary Series
60 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
HONEYWELL UNITARY INSTALLATION INSTRUCTIONS-24 VAC/VDC
31-00614-01 14
INPUT / OUTPUT WIRING
Wiring Requirements
NOTE:
When attaching two or more wires to the same
terminal, other than 14 AWG (2.0 mm
2
), be sure to twist them together. Deviation from this rule can result in
improper electrical contact.
Each terminal can accommodate the following gauge of wire:
Single wire: From 22 AWG (0.3 mm
2
) to 18 AWG (1 mm
2
) solid or stranded
Multiple wires: Up to two 18 AWG (1 mm
2
) stranded, with 1/4 watt wire-wound resistor
Prepare wiring for the terminal blocks, as follows:
Strip 1/2 in. (13 mm) insulation from the
conductor.
Cut a single wire to 3/16 in. (5 mm). Insert the wire in the required terminal location and tighten the screw.
If two or more wires are being inserted into one terminal location, twist the wires together with a minimum of
three turns before inserting them.
Cut the twisted end of the wires to 3/16 in. (5 mm) before inserting them into the terminal and tightening the
screw.
Pull-on each wire in all terminals to check for good mechanical connection.
NOTE:
Do not over-tighten the terminal screws to avoid deformation and damage to the terminal block.
The maximum torque for the terminal screws is 4.4 in-lb (0.5 Nm).
Fig. 13 Attaching Two or More Wires at Terminal Block

Table of Contents

Related product manuals