HONEYWELL UNITARY INSTALLATION INSTRUCTIONS-24 VAC/VDC
31-00614-01 8
Wire Gauge Range
Table 11 Wire Gauge Range
Solid State Relay (SSR)
Table 13 Fuse for SSRs
Relays
Table 15 Fuse for Relays
Parameter Specification
SSR output and SRIN
22-18 AWG
Relay
18-14 AWG
NOTE:
The range will depend on the current supplied.
Table 12 Solid State Relay (SSR)
Specification
SSR works with maximum 24 VAC / VDC
1.5 A constant; 3.5 A inrush for 0.1 seconds per SSR
output.
Factory installed jumper between 24 VAC or 24 VDC
supply and SSR input shared by all SSRs.
Type 1
Input
Fuse Part
Number
Current
Rate
[A]
Voltage
Rate
[A]
Holder
Part
Number
SSR
0AGC005.V 5 32 150603
0AGW005.VP 5 32 BK/HRK-R
BK/AGW-5 5 32 BK/HRK-R
Table 14 Relays
Parameter Specification
Contact Rating
Up to 240/277 VAC or 24 VDC
3 contacts per relay (Normally open
(NO), Normally closed (NC),
Common (IN)).
10 A constant current on normally
open contact and 100 A inrush for
100 ms.
Total current across all relays is
limited to 12 A if all commons are
connected via a relay jumper.
Output
240/277 VAC, 50/60 Hz, or 24 VDC,
12 A Max. total common (10 A Max.
per Relay)
Number of
Automatic
Cycles
40000 cycles for contact A (NO)
6000 cycles for contact C (CO)
Type of disconnection or interruption provided by
each circuit
Relay outputs can be used as dry contact output.
Type 1.C
Input
Fuse Part
Number
Current
Rate
[A]
Voltage
Rate
[A]
Holder
Part
Number
Relay
021812.5
MXP
12.5 250
01500520
H
0505012.MX
P
12 250 150603
FCD-12.5A 12 250
01500520
H
Table 14 Relays