EasyManua.ls Logo

Honeywell XNX-UT Series

Honeywell XNX-UT Series
207 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
XNX Universal Transmitter
Warnings/Faults
134
Note 4:
Optima and Excel fault and warning codes are displayed in the Event History data eld.
Note 5:
Subtypes Decimal Description
ECC Fault
Subtypes
1 I2C error reading or writing EEPROM
2 GALPAT RAM test failure
4 Program memory CRC failure
8 Opcode test failure
16 Can’t adjust PGA or EEPROM value doesn't match digital
pot
32 Reserved
64 Reserved
128 GALPAT RAM test failure in common area
mV Fault
Subtypes
1 I2C error reading or writing EEPROM
2 GALPAT RAM test failure
4 Program memory CRC failure
8 Opcode test failure
16
Can’t adjust PGA or EEPROM value doesn't match digital
pot
32 RAM safety variable failure
64 Interrupts integrity failure
128 Stack overow/underow failure
Note 6:
Relay Option Board Error Status
Decimal Description
Relay Option Board Error
Status
1 Didn't receive STX or ETX
2 Received undened command
4 Exceeded maximum data bytes
8 Write collision or buffer overrun
16 CRC error in SPI packet
32 Stack overow or underow
64 Program memory CRC error
128 Galpat RAM test failure

Table of Contents