XNX Universal Transmitter Quick Start Guide
65
Warning Description
Ap-
plicable
Sensors
Latching /
Non-Latching
Frequency of
Diagnostic
Event History
Data
Action For Resolution
W010
Sensor Path
Obscured
Optima Non-latching
XNX polls
sensor every
2 seconds,
diagnostic
frequency
controlled by
sensor
Sensor fault or
warning code
(Note 4)
Check location for external interference. Check sensor for dirty windows.
Beam Block Excel Non-latching
XNX polls
sensor every
2 seconds,
diagnostic
frequency
controlled by
sensor
Sensor fault or
warning code
(Note 4)
Check location for external interference or obstructions in the IR path. Check sen-
sor for dirty windows. Check Excel alignment.
W011
Sensor Internal
Lamp Issue
Optima Latching
XNX polls
sensor every
2 seconds,
diagnostic
frequency
controlled by
sensor
Sensor fault or
warning code
(Note 4)
Remove and return to Honeywell for repair.
W012 Excessive Float
Optima,
Excel
Non-latching
XNX polls
sensor every
2 seconds,
diagnostic
frequency
controlled by
sensor
Sensor fault or
warning code
(Note 4)
Check sensor location for external interference, check sensor for operation and
re-zero where appropriate.

Table of Contents

Other manuals for Honeywell XNX-UT Series

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell XNX-UT Series and is the answer not in the manual?

Honeywell XNX-UT Series Specifications

General IconGeneral
BrandHoneywell
ModelXNX-UT Series
CategoryTransmitter
LanguageEnglish

Related product manuals