EasyManua.ls Logo

Honeywell XNX-UT Series

Honeywell XNX-UT Series
207 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
XNX Universal Transmitter
Installation and Operation
57
Multidrop Mode
The multidrop mode of operation requires only a single pair of
wires and, if applicable, safety barriers and an auxiliary power
supply for up to 8 eld devices (see the illustration below). All
process values are transmitted via HART protocol. In multidrop
mode, all eld device polling addresses are >0, and the current
through each device is xed at a minimum value (typically 4 mA).
Input/Output (I/O) System
Handheld Terminal
Field Devices
Control System or
Other Host Application
Note: Instrument power is provided by an interface
or external power source that is not shown.
Figure 56. Multidrop mode of operation
Note: Use multidrop connection for supervisory control installations that are widely
spaced such as pipelines, custody transfer stations, and tank farms.
NOTE
!
In general, the installation practice for HART devices is the same
as conventional 4-20mA instrumentation. Individually shielded
twisted pair cable, either in single-pair or multi-pair varieties, is
the recommended wiring practice. Unshielded cables may be
used for short distances if ambient noise and cross-talk will not
affect communication.
The minimum conductor size is 0.51 mm diameter (#24 AWG) for
cable runs of less than 5,000 ft. (1,524 m) and 0.81 mm diameter
(#20 AWG) for longer distances.

Table of Contents

Related product manuals