XNX Universal Transmitter Quick Start Guide
57
9 Sensor Data
9.1 OperatingandStorageConditionsforPerformanceTestedECCartridges
Gas Cartridge P/N Operating Pressure
Operating Air
Speed
Warm-up Time
(minimum)
Storage Conditions*
Temperature Pressure Humidity Time**
O
2
Oxygen
XNXXSO1SS
80 kPa ~ 120 kPa 0 ~ 6 m/sec 60 sec. 0 to 20°C, 32 to 68°F 80 to 120 KPa 5 to 95% RH 6 months
XNXXSO1FM
H
2
S Hydrogen Sulfide
XNXXSH1SS
80 kPa ~ 120 kPa 0 ~ 6 m/sec 60 sec. 0 to 20°C, 32 to 68°F 70 to 110 KPa 30 to 70% RH 6 months
XNXXSH1FM
H
2
S (High) Hydrogen Sulfide XNXXSH2SS 80 kPa ~ 120 kPa 0 ~ 6 m/sec 60 sec. 0 to 20°C, 32 to 68°F 70 to 110 KPa 30 to 70% RH 6 months
CO Carbon Monoxide
XNXXSC1SS
80 kPa ~ 120 kPa 0 ~ 6 m/sec 60 sec. 0 to 20°C, 32 to 68°F 70 to 110 KPa 30 to 70% RH 6 months
XNXXSC1FM
*Store in sealed packages **Check cartridge certicates

Table of Contents

Other manuals for Honeywell XNX

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell XNX and is the answer not in the manual?

Honeywell XNX Specifications

General IconGeneral
Ingress ProtectionIP66/67
Product TypeUniversal Transmitter
Enclosure RatingIP66/67
DisplayLCD
Communication ProtocolsHART, Modbus, Foundation Fieldbus
Power Supply24 VDC nominal, 18-32 VDC
Operating Temperature-40°C to +65°C (-40°F to +149°F)
MaterialAluminum or Stainless Steel
Gas TypesToxic, Oxygen, and Combustible gases
Output4-20 mA
Relays3 programmable relays
ApprovalsATEX, IECEx, UL, CSA
Sensor CompatibilityElectrochemical, catalytic, infrared, and other sensor types