9 Sensor Data
9.1 OperatingandStorageConditionsforPerformanceTestedECCartridges
Gas Cartridge P/N Operating Pressure
Operating Air
Speed
Warm-up Time
(minimum)
Storage Conditions*
Temperature Pressure Humidity Time**
O
2
Oxygen
XNXXSO1SS
80 kPa ~ 120 kPa 0 ~ 6 m/sec 60 sec. 0 to 20°C, 32 to 68°F 80 to 120 KPa 5 to 95% RH 6 months
XNXXSO1FM
H
2
S Hydrogen Sulfide
XNXXSH1SS
80 kPa ~ 120 kPa 0 ~ 6 m/sec 60 sec. 0 to 20°C, 32 to 68°F 70 to 110 KPa 30 to 70% RH 6 months
XNXXSH1FM
H
2
S (High) Hydrogen Sulfide XNXXSH2SS 80 kPa ~ 120 kPa 0 ~ 6 m/sec 60 sec. 0 to 20°C, 32 to 68°F 70 to 110 KPa 30 to 70% RH 6 months
CO Carbon Monoxide
XNXXSC1SS
80 kPa ~ 120 kPa 0 ~ 6 m/sec 60 sec. 0 to 20°C, 32 to 68°F 70 to 110 KPa 30 to 70% RH 6 months
XNXXSC1FM
*Store in sealed packages **Check cartridge certicates