Loading...
Table 26 EVA8400 UPS loading
% of UPS capacity
WattsEnclosures
R12000R5500
41.0492012
36.898.1441411
33.689.7403710
30.581.336609
27.473.032848
24.264.629077
21.156.225306
17.947.921535
14.839.517774
11.731.114003
8.522.710232
5.414.46471
Table 27 EVA6400 UPS loading
% of UPS capacity
WattsEnclosures
R12000R5500R3000
26.871.432148
23.663.028377
20.554.691.124606
17.346.277.220835
14.237.963.217074
11.129.549.313303
7.921.235.39532
4.812.821.45771
Shock and vibration specifications
Table 28 (page 109) lists the product operating shock and vibration specifications. This information
applies to products weighing 45 Kg (100 lbs) or less.
NOTE: HP P6000 EVA products are designed and tested to withstand the operational shock and
vibration limits specified in Table 28 (page 109). Transmission of site vibrations through non-HP
racks exceeding these limits could cause operational failures of the system components.
Table 28 Operating Shock/Vibration
Shock test with half sine pulses of 10 G magnitude and 10 ms duration applied in all three axes (both positive and
negative directions).
Sine sweep vibration from 5 Hz to 500 Hz to 5 Hz at 0.1 G peak, with 0.020” displacement limitation below 10
Hz. Sweep rate of 1 octave/minute. Test performed in all three axes.
Environmental and operating specifications 109