2. User Interface
Continued
Description
Available settings
Default settings
In/Out settings
Load segments - Auto
shutdown delay
[Disable] [0s] [1 s] [2 s]…[65354 s]
During a power outage, this setting
enables the UPS to turn off power to
equipment connected to Group 1 and/or
Group 2 outlets, or disables the action.
This feature sheds non-critical loads in
order to conserve battery power for critical
loads connected to the primary group.
Group 1: Disable
Group 2: Disable
Overload
prealarm
[5%] [10%] [15%] [20%] ... [100%] [105%]
Sets alarm for critical percentage of load
where alarm overload occurs.
[105 %]
ON/OFF settings
Cold start [Disable] [Enable]
Enables or disables the product to start
on battery. The first cold start is always
disabled.
Enable
Forced reboot [Disable] [Enable]
If enabled and power returns during
a shutdown sequence, the shutdown
sequence will complete and there is a 10
second delay prior to restart.
If disabled, shutdown sequence does not
complete and restart occurs immediately.
Enable
Auto restart [Disable] [Enable]
Enables or disables the UPS to restart
automatically when power returns after a
complete battery discharge.
Enable
Energy saving [Disable] [Enable]
If enabled, the UPS will shutdown after
five minutes if no load is detected on the
output.
Disable
Sleep mode [Disable] [Enable]
If enabled, LCD and communication stays
on 1h and 30 min after UPS turns off.
If disabled, LCD and communication will
turn off immediately after the UPS turns
off.
Disable
Remote command [Disable] [Enable]
If enabled, shutdown or restart commands
from software are allowed.If disabled, shut-
down or restart commands from software
are not allowed.
Enable
Battery settings
Automatic battery test [No test] [Every day] [Every week] [Every
month]
Available only if Battery Charge mode is
set to constant charge.
Every week
(in constant charge)
otherwise following EBM
Low battery
warning
[10%] [20%] [30%] [40%] [50%] [60%]
[70%] [80%] [90%]
The alarm occurs when the value set
for the low battery capacity warning is
reached.
20%
Restart battery level [10%] [20%] [30%] [40%] [50%] [60%]
[70%] [80%] [90%] [100%]
If set, automatic restart occurs only when
the percentage of battery charge you
specify is reached.
0%
Battery charge mode [EBM cycling] [Constant charge] EBM cycling
ERM number
setting
[0] [1] [2] [3] [4]
Using standard ERM, the UPS automatically
detects the number of connected ERMs.
ERM automatic detection,
otherwise 0
Deep discharge protec-
tion
[Yes] [No]
If set to Yes, the UPS automatically pre-
vents the battery from deep discharge by
adapting the end of back-up time voltage
threshold.
Yes