Installation and configuration 25
Connecting the UPS cord retention clips
Charging the UPS batteries
With the UPS in Standby mode, allow the batteries to charge before putting the UPS into service.
IMPORTANT: Charge the batteries for at least 24 hours before supplying backup power to
devices. The batteries charge to:
80 percent of their capacity within 3 hours
100 percent of their capacity within 48 hours
Starting power to the load
Start power to the load by placing the UPS in Operate mode.
IMPORTANT: AC power must be available the first time the UPS is started.
Configuring the UPS Network Module
NOTE: For more information about the UPS Network Module, see the HP Infrastructure
Management Pack software CD and documentation for complete details.
Before configuring the UPS Network Module, be sure that the network cable is connected.
Connecting the configuration cable
1. Connect the DB-9 connector on the DB-9 to RJ-45 cable to a serial connector on the host computer.