64 |
F1 AUS
This value sets the relative humidity at which relay F1 should switch off.
Setting range: 0 to 100%
Factory setting: 60%
REL F1 delay
The function REL F1 delay sets the switch-on delay for the relay F1.
This setting prevents frequent switching of the relay F1, if with slightly fl uctuating
humidity values, the setpoints F1 ON or F1 OFF have almost the same values.
Setting range: 0 to 60 sec.
Factory setting: 0 sec.
F2 EIN
This value sets the relative humidity at which the relay F2 is to switch on.
Setting range: 0 to 100%
Factory setting: 70%
F2 AUS
This value sets the relative humidity at which the relay F2 should switch off.
Setting range: 0 to 100%
Factory setting: 60%
REL F2 delay
The function REL F2 delay sets the switch-on delay for the relay F2.
This setting prevents frequent switching of the relay F2, if with slightly varying
humidity values, the setpoints F2 ON or F2 OFF have almost the same values.
Setting range: 0 to 60 sec.
Factory setting: 0 sec.
Modes/ functions