Professional humidity switch PLS1000
T1 AUS
The switch-off temperature indicates at which temperature the relay T1 should
be switched off.
Setting range: -40°C to +120°C
Factory setting: 22°C
REL T1 delay
The function REL T1 delay sets the switch-on delay for the relay T1.
This setting prevents frequent switching of the relay T1, if the values T1 ON or
T1 OFF are almost identical at slightly fl uctuating temperatures.
Setting range: 0 to 60 sec.
Factory setting: 0 sec.
T2 EIN
The switch-on temperature indicates from which temperature the relay T2 should
be switched on.
Setting range: -40°C to +120°C
Factory setting: 23°C
T2 AUS
The switch-off temperature indicates at which temperature the relay T2 should
be switched off.
Setting range: -40 °C to +120 °C
Factory setting: 22 °C
REL T2 delay
The function REL T2 delay sets the switch-on delay for the relay T2.
This setting prevents frequent switching of the relay T2, if the values T2 IN and
T2 OFF are almost identical with slightly fl uctuating temperatures.
Setting range: 0 to 60 sec.
Factory setting: 0 sec.
F1 EIN
This value is used to set the relative humidity at which relay F1 should switch on.
Setting range: 0 to 100%
Factory setting: 70%
L(Phase)
N(Zero)
62 |
Anschlussbeispiel
8.4 TF-Schalter
Beispiel:
Lüfter soll bei einer Innentemperatur von 35 °C
und einer relativen Luftfeuchte von 70 % und wenn
die Außentemperatur unter 30 °C und die relative Feuchte unter 60 % fällt, einschalten.
Einstellungen: T1 Ein = 35 °C, T1 Aus = 34 °C
Einstellungen: F1 Ein = 70 % , T 1 Aus = 60 %
Einstellungen: T2 Ein = 30 °C , T2 Aus = 31 °C
Einstellungen: F2 Ein = 60 %, F2 Aus = 70 %
Hinweis: Der Feuchtesensor T1 wird im Raum montiert
Der Feuchtesensor T2 wird außen montiert
N (Null)
L (Phase)
Netz 230V/50 Hz
Zuluft
(Lüfter 230V~)
The parameters have the following meaning:
T1 EIN
The switch-on temperature controls at which temperature the relay T1 should
be switched on.
Setting range: -40°C to +120°C
Factory setting: 23°C
Example:
Fan should switch on at an indoor temperature of 35°C and
a relative humidity of 70 % and when the outside temperature falls
below 30°C and the relative humidity below 60%.
Settings T1 On = 35°C, T1 Off = 34°C
Settings F1 On = 70 %, F1 Off = 60 %
Settings T2 On = 30°C, T2 Off = 31°C
Settings F2 On = 60 %, F2 Off = 70 %
Note: Sensor T1 is installed inside the room
Sensor T2 is to be installed outside
Connection example:
Mode 7.4 „TF switch
Supply air
(fan 230~)
Mains 230V/50Hz
S = normally open contact
W = change-over contact
O
= normally closed
contact
Modes/ functions
L(Phase)
N(Zero)

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the HTRONIC PLS 1000 and is the answer not in the manual?

HTRONIC PLS 1000 Specifications

General IconGeneral
BrandHTRONIC
ModelPLS 1000
CategorySwitch
LanguageEnglish

Related product manuals