6.2 Powering On the EMMA
● Wear personal protective equipment and use dedicated insulated tools to avoid
electric shocks or short circuits.
Before the equipment is put into operation for the rst time, ensure that the
parameters are set correctly by professional personnel. Incorrect parameter
settings may result in noncompliance with local grid connection requirements and
aect the normal operations of the equipment.
Procedure
Step 1 Turn on the main circuit breaker between the EMMA and the grid.
Step 2 Turn on the AC switch between the EMMA and the inverter.
Step 3 Observe the LED indicators on the EMMA to check its running status.
Table 6-1 LED indicator description
Indicator
Status Description
Running
status
indicator
O The EMMA is not powered on.
Steady green The EMMA is powered on and running.
Alarm
indicator
O No alarm is raised.
Blinking red
slowly (on for 1s
and then o for
4s)
A warning or minor alarm is generated.
Blinking red fast
(on for 0.5s and
then o for
0.5s)
A major alarm is generated.
Steady red A critical alarm is generated.
EMMA-(A01, A02)
User Manual 6 Power-On and Commissioning
Issue 05 (2024-01-19) Copyright © Huawei Digital Power Technologies Co., Ltd. 41