FusionModule500 Smart Mini Data Center
Product Description (ECC800e)
3 System Architecture
Copyright © Huawei Technologies Co., Ltd.
22
Figure 3-2 Power distribution conceptual diagram for the 220 V single-phase scenario with the 6
kVA/10 kVA UPS
The power distribution system meets the power supply requirements of single-phase 220
V/230 V/240 V.
Table 3-2 Power distribution system technical specifications
Item
Specifications (10
kVA UPS)
Specifications (6
kVA UPS)
Specifications (3
kVA UPS)
Rated power
9 kW
5.4 kW
2.7 kW
Rated input voltage
220 V/230 V/240 V
220 V/230 V/240 V
220 V/230 V/240 V
Rated frequency
50 Hz/60 Hz
50 Hz/60 Hz
50 Hz/60 Hz
Maximum input
current
50 A
32 A
19 A
External input
power distribution
circuit breaker
63 A
50 A
32 A