PowerCube 5000 (SUN2000-150KTL-S0)
Installation Guide
9 Power-on and Commissioning
Copyright © Huawei Technologies Co., Ltd.
Table 9-7 Setting the Network Param.
Path
Parameters
Default Value
Setting
Settings Wizard
IP Address
192.168.0.10
Set this parameter
based on the address
assigned by the
network
administrator.
Subnet Mask
255.255.255.0
Set this parameter
based on the address
assigned by the
network
administrator.
Default Gateway
192.168.0.1
Set this parameter
based on the address
assigned by the
network
administrator.
Step 2 After the wizard setting is complete, the SMU accesses the main menu.
The parameter values in the figures are for reference only.
Figure 9-2 Main menu
If no button is pressed in 1 minute on any screen, the MDU touchscreen will turn off. The main
menu will be displayed if the MDU touchscreen is tapped again.
You can tap the bypass, PV, load, or battery icon on the main menu to view the running information
about the corresponding component. You can also tap Common Functions or System Info to view
or set parameters.
is the start/stop button used to control system output.
Step 3 When the SMU is running properly, you can choose the following menus to change the MDU
language.