What does 'Grid overfrequency' mean on my Huawei SUN2000-30KTL-M3?
- MMichael BlakeSep 1, 2025
A 'Grid overfrequency' alarm on a Huawei Inverter indicates a power grid exception where the actual power grid frequency is higher than the requirements for the local power grid code. If the alarm occurs occasionally, it might be a temporary power grid issue, and the inverter should recover automatically. If the alarm persists, verify that the power grid frequency is within the acceptable range. If it's not, contact the local power operator. If the frequency is within range, consider modifying the grid overfrequency protection threshold via the app, SmartLogger, or NMS, with the consent of the local power operator.