Step 6 Log in to the app, choose Maintenance > Inverter ON/OFF on the home screen,
and send a shutdown command. Set DC SWITCH to OFF, reconnect the
disconnected PV module and optimizer, and repeat Step 5 to check the PV
modules and optimizers adjacent to the possible fault location.
Step 7 Determine the position of the ground insulation fault:
● Disconnect the possible faulty PV module from the optimizer.
● Connect the possible faulty optimizer to the PV string.
● Set DC SWITCH to ON. If the inverter status is Shutdown: Command, choose
Maintenance > Inverter ON/OFF, and send a startup command. View alarm
information.
– If no Low insulation resistance alarm is reported 1 minute after the DC
side is powered on, the fault is on the possible faulty PV module.
– If the Low insulation resistance alarm is reported 1 minute after the DC
side is powered on, the fault is on the possible faulty optimizer.
● Log in to the app, choose Maintenance > Inverter ON/OFF on the home
screen, and send a shutdown command. Set DC SWITCH to OFF, replace the
faulty component, and complete troubleshooting the insulation resistance
fault. Go to Step 2 and check rest of the PV strings one by one. Then, go to
Step 8.
Step 8 Set DC SWITCH to ON. If the inverter status is Shutdown: Command, choose
Maintenance > Inverter ON/OFF, and send a startup command.
----End