TP48200A-DX12A1 Telecom Power
User Manual
A Technical Specifications
Copyright © Huawei Technologies Co., Ltd.
54
A Technical Specifications
A.1 Environment Specifications
Table A-1 Environment specifications
Item
Specifications
Operating temperature
33ºC to +40ºC with 1120 W/m
2
solar radiation
Transport temperature
40ºC to +70ºC
Storage temperature
40ºC to +70ºC
Operating humidity
5%95% RH
Storage humidity
5%95% RH
Altitude
04000 m
When the altitude ranges from 2000 m to 4000 m, the operating
temperature decreases by 1°C for each additional 200 m.
Others
There should be no conductive dust, corrosive gas, or explosion
hazard.
Dust, corrosive substances, pests, molds, and other indicators should
be controlled in accordance with class 4.1 requirements in ETSI EN
300 019-1-4 (V2.2.1).
A.2 Electrical Specifications
Table A-2 Electrical specifications
Item
Specifications
AC input
Input system
220/380 V AC three-phase
Input voltage
85300 V AC