Item Data Plan for the
F01D500 Cabinet
Remarks
Delays the time of the
discharging test: 1d
This parameter is set according to the actual
requirements.
Default: 14d.
Rectifier unit
parameter
Number of rectifier
units: 2
This parameter is set according to the actual
requirements. The EPS75-4815AF supports up to
two rectifier units.
Default value: 5.
Load and
battery high-
temperature
power-off
parameters
Load high-temperature
power-off permission
status: forbid
This parameter is set according to the actual
requirements.
Default: forbid.
Battery high-
temperature power-off
permission status: permit
This parameter is set according to the actual
requirements.
Default: forbid.
Temperature for load
high-temperature
power-off: 70°C
This parameter is set according to the actual
requirements.
Default: 65°C.
Temperature for battery
high-temperature
power-off: 53°C
This parameter is set according to the actual
requirements.
Default: 53°C.
Environment
monitoring
parameters
Upper alarm threshold of
the temperature: 68°C
This parameter is set according to the actual
requirements. When the actual temperature
reaches or is higher than the upper alarm
threshold, the system reports an alarm.
Default: 50°C.
Lower alarm threshold
of the temperature: -5°C
This parameter is set according to the actual
requirements. When the actual temperature is
equal to or lower than the lower alarm threshold,
the system reports an alarm.
Default: 0°C.
Upper alarm threshold of
the humidity: 80% RH
This parameter is set according to the actual
requirements. When the actual humidity reaches
or is higher than the upper alarm threshold, the
system reports an alarm.
Default: 80% RH.
Lower alarm threshold
of the humidity: 10% RH
This parameter is set according to the actual
requirements. When the actual humidity is equal
to or lower than the lower alarm threshold, the
system reports an alarm.
Default: 10% RH.
UA5000 Universal Access Unit
Environment Monitoring 7 EPS75-4815AF Monitoring Solution