EasyManua.ls Logo

Huawei UA5000 - Page 125

Huawei UA5000
209 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
battery temperature alarm upper: 50C battery temperature alarm lower: 0C
load off permit : forbid load off voltage : 44.000V
battery off permit : permit battery off voltage : 43.000V
AC over alarm voltage : 280V AC lack alarm voltage : 180V
DC over alarm voltage : 58 V DC lack alarm voltage : 45V
power module number: 2
module 0 address: 1 module 0 switch state : On
module 1 address: 2 module 1 switch state : On
Load high-temperature-off permit: forbid
Load high-temperature-off temperature(C): 70
Battery high-temperature-off permit: permit
Battery high-temperature-off temperature(C): 53
----------------------------------------------------------------------------
huawei(config-if-power4875l-0)#display power environment parameter
EMU ID: 2 Power environment configration
parameter
----------------------------------------------------------------------------
AnalogID Name AlmUpper AlmLower TestUpper TestLower Unit
Type
0 Temperature 68 -5 80 -20 C
Current
1 Humidity 80 10 100 0 %R.H.
Current
----------------------------------------------------------------------------
DigitalID Name Level |DigitalID Name
Level
0 Fan 0 | 1 HABF_FAN
0
2 - 0 | 3 SPD
1
4 Smoke 1 | 5 HEX
0
6 MDF-door
0
----------------------------------------------------------------------------
15. Query the alarms, and confirm that the door status alarm other than alarms for other
monitoring parameters is generated.
huawei(config-if-power4875l-0)#display power alarm
EMU ID: 0 Power alarm information
----------------------------------------------------------------------------
Mains supply yes : Yes Mains supply lack : Normal
Total Vol lack : Normal
Load fuse 0 : Connect Second fuse : Connect
Load off : On Battery off : On
Battery 0 loop : Disconnect
Environment Temperature : Normal Environment Humidity : Normal
Door alarm : Alarm Water alarm : Normal
Fog alarm : Normal Wiring alarm : Normal
Module 0 : Normal
Module 1 : Normal
Module 2 : Normal
Battery temperature off state : Normal Load temperature off state : Normal
----------------------------------------------------------------------------
Name State |Name State
Spare Dig0(Fan) Normal|Spare(HABF_FAN)
Normal
Spare Dig2 Normal|Spare Dig3(SPD)
Normal
Spare Dig4(Smoke) Normal|Spare Dig5(HEX) Alarm
Spare Dig6(MDF-door) Alarm
----------------------------------------------------------------------------