Specifications
Table 6-8 lists the specifications of the EPS30-4815AF power system.
Table 6-8 Specifications of the EPS30-4815AF power system
Parameter
Specification
Input
l Rated input voltage: 220 V AC (90-290 V AC) (Note that
in the range of 90-176 V AC, the output current also
decreases linearly, limited within a specified range.)
l Maximum input current: 10 A
l Frequency: 50 Hz (45-65 Hz)
Output
l Rated output voltage: -53.5 V DC
l Voltage range: -43.2 V DC to -57.6 V DC
l Output current:
– LOAD1: 10 A (fuse)
– LOAD2: 20 A (fuse)
– BATT: 20 A (fuse)
Efficiency
≥ 89% (in rated working state, 50% to 100% load)
Operating temperature range -33°C to +65°C (Note that in the range of +50°C to +65°C,
the output current also decreases linearly, limited within a
specified range.)