Figure 4-41 Marking-o template (unit: mm)
(1) Rear edge of the cabinet (2) Wall
(3) Mounting holes for antiseismic kits (4) Mounting hole of the L-shaped bracket
Pay attention to the front and back edge lines of the cabinet, preventing incorrect location.
Step 2 Use a hammer drill to drill holes for installing expansion bolts and then install
expansion sleeves in the holes.
1. Drill a hole into the concrete oor using a hammer drill. The hole depth
ranges from 52 mm to 60 mm.
2. Slightly tighten the expansion bolt and vertically insert it into the hole. Knock
the expansion bolt using a rubber mallet until the expansion sleeve is fully
inserted into the hole.
3. Partially tighten the expansion bolt.
4. Remove the bolt, spring washer, and at washer.
Knock the expansion bolt into the hole until the expansion sleeve completely ts
into the hole. The expansion sleeve must be completely buried under the ground
to facilitate subsequent installation.
UPS5000-A-(30 kVA-120 kVA)
User Manual 4 Installation and Cable Connection
Issue 17 (2024-02-21) Copyright © Huawei Digital Power Technologies Co., Ltd. 94