Figure 4-46 Installing a reinforced beam (front view)
Step 3 Use scale plates to determine the installation positions of oating nuts at the left
and right sides on the front of the rack, and install oating nuts.
NO TICE
Level the Bottom line on the scale plate with the lower edge of U sale 01 on the
rack. Install oating nuts onto the mounting holes for the mounting bar that
corresponds to Hole location lines.
UPS5000-A-(30 kVA-120 kVA)
User Manual 4 Installation and Cable Connection
Issue 17 (2024-02-21) Copyright © Huawei Digital Power Technologies Co., Ltd. 98