No. Item Acceptance Criteria
13 Operating environment The inside and outside of the cabinet are
free from conductive dust or other
sundries.
● 30 kVA/40 kVA UPS
– There is no foreign matter (such as
copper wires and screws) between
wiring terminals. Cables are
crimped according to standards,
and there is no bare copper wire.
– There is no foreign matter in the
wiring terminal box.
● 60 kVA/80 kVA/120 kVA UPS
– There is no foreign matter
between wiring terminals. Cables
are crimped according to
standards, and there is no bare
copper wire.
– There is no foreign matter at the
bottom of the UPS.
14 DIP switch settings Toggle switch 4 is set to ON.
15 Short circuit between
copper bars
Check that copper bars are open-
circuited using a multimeter.
● If the equipment will not be powered on after installation, take dustproof
measures (for example, use a dust cover) to prevent equipment damage due to
dust buildup inside it. Remove the dust cover only when the equipment is ready
for operation.
● After the installation is complete, take anti-condensation measures and keep
the air conditioner running. Do not store the equipment in an environment
where the temperature and humidity are uncontrollable for a long period of
time. Otherwise, the equipment may be damaged due to condensation.
● After installing cables and verifying the installation, use sealing putty to seal
the gaps between the cables and the cabinet.
● Use the sealing putty delivered with the equipment to seal the cabinet.
● Do not remove the transparent lm.
● If the sealing putty covers the aluminum foil lm, do not cut the sealing
putty.
● After verifying the installation, reinstall all the covers.