No. Check Item Acceptance Criteria Check Method and
Troubleshooting
Check
Interval
6 Ambient
humidity
Actual humidity: ______%
RH (0%–95% RH, non-
condensing)
● Check method:
Measure using a
hygrothermograph.
● Troubleshooting: Check
that the air conditioner
runs properly.
Monthly
Product Component Checklist
No. Check Item Acceptance Criteria Check Method and
Troubleshooting
Check
Interval
1 Installation The equipment is installed
properly and arranged
neatly, and screws are
tightened.
● Check method: visual
inspection
● Troubleshooting:
Rectify the fault based
on the acceptance
criteria.
Monthly
2 Appearance ● Wipe the device surface
using a white paper
and the paper does not
turn black.
● The equipment is not
rusty or deformed.
● Check method: visual
inspection
● Troubleshooting:
Rectify the fault
according to the
acceptance criteria.
Clean up the dust on
the air lter or replace
the air lter during
dust removal.
Quarterly
3 Cabinet cable
hole
protection
The cable holes of the
cabinet have been fully
sealed using the standard
sealing plates, and rodent-
proof measures are taken.
● Check method: visual
inspection
● Troubleshooting:
Rectify the fault based
on the acceptance
criteria.
Quarterly
4 Air outlet The air outlet is not
blocked.
● Check method: visual
inspection
● Troubleshooting:
Rectify the fault based
on the acceptance
criteria.
Quarterly
UPS5000-A-(30 kVA-120 kVA)
User Manual 7 Maintenance
Issue 17 (2024-02-21) Copyright © Huawei Digital Power Technologies Co., Ltd. 142