Running Status Checklist
No. Check Item Acceptance Criteria Check Method and
Troubleshooting
Check
Interval
1 Working
status
The UPS LCD shows that
all batteries are running
properly, battery running
parameters are within
their normal ranges, and
no battery fault or alarm
information is displayed.
Check method: Visual
inspection. Check the
system status on the
UPS LCD.
Troubleshooting: View
the alarm information
on the LCD and handle
the alarm.
Monthly
2 Battery
temperature
sensor
precision
The deviation between the
detected temperature and
the displayed temperature
is less than 3°C.
Check method: Visual
inspection using a
hygrothermograph.
Troubleshooting:
Correct the installation
position of the battery
temperature sensor, or
replace the sensor.
Quarterly
3 Battery
management
parameters
Battery management
parameter settings and
battery charge and
discharge conditions
meet the requirements
of the battery
manufacturer.
The battery operating
temperature is lower
than the ambient
temperature plus 20°C.
Check method: Visual
inspection. Check the
parameters displayed
on the UPS LCD.
Troubleshooting:
Correct the parameter
settings or rectify
battery operating
temperature
abnormality.
Quarterly
UPS5000-A-(30 kVA-120 kVA)
User Manual 7 Maintenance
Issue 17 (2024-02-21) Copyright © Huawei Digital Power Technologies Co., Ltd. 148