CA UTION
Cables and terminals must match each other. For example, cables with a cross-
sectional area of 16 mm
2
must be used with terminals whose nominal cross-
sectional area is 16 mm
2
, and terminals of other models are not allowed.
To prevent short circuits, refer to the following tables for the specications
when selecting OT and DT terminals.
When preparing cables, use OT or DT terminals that match the cable cross-
sectional areas to prevent copper core exposure, which may cause arcing
between cables and consequently result in safety risks.
Table 4-1 Recommended cross-sectional areas for power cables
Item 30
kVA
40 kVA 60 kVA 80
kVA
120 kVA
Mains
input
Mains input current
(A)
53 71 UPS5000-
A-60KTTL-H: 96
UPS5000-
A-60KTTL: 107
142 UPS5000-
A-120KTTL-H:
191
UPS5000-
A-120KTTL:
213
Recomme
nded
cross-
sectional
area
(mm
2
)
L1 4 x 10 4 x 16 4 x 35 4 x 50 4 x 95
L2
L3
N
Bypass
input
Bypass input current
(A)
46 61 91 122 182
Recomme
nded
cross-
sectional
area
(mm
2
)
L1 4 x 10 4 x 16 4 x 35 4 x 35 4 x 70
L2
L3
N
Output Output current (A) 46 61 91 122 182
Recomme
nded
cross-
sectional
area
(mm
2
)
U 4 x 10 4 x 16 4 x 25 4 x 35 4 x 70
V
W
UPS5000-A-(30 kVA-120 kVA)
User Manual 4 Installation and Cable Connection
Issue 17 (2024-02-21) Copyright © Huawei Digital Power Technologies Co., Ltd. 66